Details
Approvals:
ARRA Compliant|Buy American Act Compliant|RoHS Compliant|CSA File No.LR43364/3211 04/C22.2 No.14|EN 60947-4-1/60947-5-1|IEC 60647-4/60947-4-1/60947-5-1|UL File No.E164862/NLDX/508|BV Certified|CE Marked|CCC Certified|DNV Approved|GL Certified|GOST Certifie
Coil Power Rating:
70 VA Inrush/7.5/7 VA Hold-In
Dimensions:
3.35 in H x 1.77 in W x 3.62 in D
Number of Auxiliary Contacts:
Manufactured By:
Schneider Electric Square D
Other Details
-4 to 158 deg F permissible ambient air temperature around the device, -76 to 176 deg F storage temperature
1562 deg F conforming to IEC 60695-2-1 fire resistance
17 VAC signaling circuit minimum switching voltage
2 to 3 W at 60 Hz heat dissipation
2.5 MOhm at 50 Hz, Ith 25 A power circuit average impedance
25 A at 140 deg F power circuit/10 A at 140 deg F signaling circuit conventional free air thermal current
25 A gG at 690 V coordination type 2 power circuit/40 A gG at 690 V coordination type 1 power circuit/10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
25 to 400 Hz signaling circuit frequency
250 A at 440 V power circuit conforming to IEC 60947 rated breaking capacity
250 A at 440 V power circuit conforming to IEC 60947/140 A AC signaling circuit conforming to IEC 60947-5-1/250 A DC signaling circuit conforming to IEC 60947-5-1 Irms rated making capacity
3600 cycles/hr at 140 deg F operating rate
4 to 19 ms opening/12 to 22 ms closing operating time
5 mA minimum switching current
7.5 to 7 VA at 68 deg F 50/60 Hz hold-in power consumption
70 VA at 68 deg F 50/60 Hz inrush power
V1 conforming to UL94 flame retardant
Vibrations contactor open 2 gn, 5 to 300 Hz/vibrations contactor closed 4 gn, 5 to 300 Hz/shocks contactor closed 15 gn for 11 ms and shocks contactor open 6 gn for 11 ms mechanical robustness
Without built-in suppressor module coil technology