Details
APPLICATION:
For motor control and resistive load
Approvals:
ARRA Compliant|Buy American Act Compliant|RoHS Compliant|CSA File No.LR43364/3211 04|IEC 60947/VDE 0660|BS 5424|NF C 63-110|UL File No.E164862/NLDX2|CE Marked|PROP65: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, w
Dimensions:
2.28 in H x 3.54 in W x 2.24 in D
Number of Auxiliary Contacts:
Manufactured By:
Schneider Electric Square D
Other Details
>10 MOhm signaling circuit insulation resistance
0.02 in non-overlap distance
1.3 N-m on screw clamp terminals with screwdriver Philips No 2/flat 6 mm Dia tightening torque
10 to 20 ms coil de-energization and NO opening/coil energization and NO closing operating time
17 VAC signaling circuit minimum switching voltage
20 A at 122 deg F power circuit, 10 A at 122 deg F signaling circuit conventional free air thermal current
25 A gG at 440 V power circuit/25 A aM power circuit/10 A gG signaling circuit conforming to IEC 60947/10 A gG signaling circuit conforming to VDE 0660 associated fuse rating
3 MOhm at 50 Hz, Ith 20 A power circuit average impedance
30 VA at 68 deg F inrush power
3600 cycles/hr operating rate
4 kW at 380 to 415 VAC 50/60 Hz, 4 kW at 440 VAC 50/60 Hz, 4 kW at 480 VAC 50/60 Hz, 4 kW at 500 to 600 VAC 50/60 Hz rated power
4.5 VA at 68 deg F hold-in power consumption
400 Hz signaling circuit frequency
5 mA minimum switching current
6561.68 ft (2000 m) without derating in temperature operating altitude
8 kV rated impulse withstand voltage