Details
APPLICATION:
For motor control and resistive load
Approvals:
ARRA Compliant|Buy American Act Compliant|RoHS Compliant|CSA File No.LR43364/3211 04/C22.2 No.14|EN 60947-4-1/60947-5-1|IEC 60647-4/60947-4-1/60947-5-1|UL File No.E164862/NLDX/508|BV Certified|CE Marked|CCC Certified|DNV Approved|GL Certified|GOST Certifie
Dimensions:
3.03 in H x 3.54 in W x 3.39 in D
Number of Auxiliary Contacts:
Manufactured By:
Schneider Electric Square D
Other Details
-40 to 158 deg F permissible ambient air temperature around the device, -76 to 176 deg F storage temperature
1.5 ms on de-energization (between NC and NO contacts)/1.5 ms on energization (between NC and NO contacts) non-overlap time, >10 MOhm signaling circuit insulation resistance
17 VAC signaling circuit minimum switching voltage, TH protective treatment
2 to 3 W heat dissipation
2.5 MOhm at 50 Hz, Ith 25 A power circuit average impedance
20 A gG at 690 V coordination type 2 power circuit/25 A gG at 690 V coordination type 1 power circuit/10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
25 A at 140 deg F power circuit/10 A at 140 deg F signaling circuit conventional free air thermal current
25 to 400 Hz signaling circuit frequency
250 A at 440 V power circuit conforming to IEC 60947 rated breaking capacity
250 A at 440 V power circuit conforming to IEC 60947/140 A AC signaling circuit conforming to IEC 60947-5-1/250 A DC signaling circuit conforming to IEC 60947-5-1 Irms rated making capacity
3600 cycles/hr at 140 deg F operating rate
4 to 19 ms opening/12 to 22 ms closing operating time
5 mA minimum switching current
6 kV conforming to IEC 60947 rated impulse withstand voltage
7.5 VA at 68 deg F 60 Hz/7 VA at 68 deg F 50 Hz hold-in power consumption
70 VA at 68 deg F 50/60 Hz inrush power
Preassembled with reversing power busbar