Details
Application:
Specially designed to meet National Electrical Code Article 370-28(a) (2) for angle pulls where the distance between the raceway entry and the opposite wall of the fitting must be at least six times the trade diameter of the raceway. A pull box with easy
Material:
Aluminum, Copper Free (less than 4/10 of 1%)
Special Features:
Large cover opening (length of opening exceeds six times the trade diameter of the hub size) for easy access to conductors. Cover and gasket included. Volume is 34 cu. in.
Type:
40% Fill Conduit Body With Cover & Gasket
Manufactured By:
Killark, a Hubbell affiliate