Each completely assembled set consists of Load-Pickup Tool, JumperClamp, 15kV Jumper Cable and cable connectors. Load-Pickup Tool andJumper Clamp fit conductors from #6 Copper (0.162") through 795 ACSRkcmil (1.162"). Load-Pickup Tool cannot be used to break loads becauseoperator cannot open contacts while Tool is installed on conductor. Torecock contacts, operator inserts fiberglass rod through head of Tool topush plunger to fully-opened position. Rod is supplied attached to endof operating lanyard. Pulling this insulated lanyard closes the spring-loaded contacts. Contacts cannot be #teased# closed. Bearing-typefloating washers in jaws of Tool and Jumper Clamp assure secure grippingbut minimal scoring of conductors during installation. WARNING: Adequaterubber gloves must be worn when using this equipment. Clean and inspectLoad-Pickup Tool after every 25 operations or at least once every 90days. Clean all plastic parts with a soft cloth dampened with only ethylalcohol. To disassemble Tool, simply remove two sc